DSCA39

Analog Input Signal Conditioner DIN Rail Output Modules

Dataforth

  • Accepts High-Level Voltage Input
  • 1500 Vrms Transformer Isolation
  • True 3-Way Isolation
  • Accuracy: ± 0.03% or ± 0.05%
  • ANSI/IEEE C37.90.1 Transient Protection
  • Output Protected to 240VAC Continuous
  • Easily Mounts on Standard DIN Rail

Details

Each DSCA39 current output module provides a single channel of analog output. The input signal is buffered, isolated, filtered and converted to a unipolar or bipolar current output (Figure 1). Signal filtering is accomplished with a fivepole filter which provides 100dB per decade of attenuation above 1kHz. An anti-aliasing pole is located on the system side of the isolation barrier, and the other four poles are on the field side. After the initial system-side filtering, the input signal is chopped by a proprietary chopper circuit. Isolation is provided by transformer coupling, again using a proprietary technique to suppress transmission
of common mode spikes or surges.

Special output circuits provide protection against accidental connection of power-line voltages up to 240VAC and against transient events as defined by ANSI/IEEE C37.90.1. Protection circuits are also present on the signal input and
power input terminals to guard against transient events and power reversal. Signal and power lines are secured to the module using screw terminals which are in pluggable terminal blocks for ease of system assembly and reconfiguration. The modules have excellent stability over time and do not require recalibration,
however, zero and span settings are adjustable up to ±5% to accommodate situations where fine-tuning is desired. The adjustments are made using potentiometers located under the front panel label and are non-interactive for ease of use.

Specifications

Input Type
0 - 10 V DC
±10 V DC
0 - 20 mA
# of Inputs
1
Output Type
0 - 20 mA
4 - 20 mA
±20 mA
Max Bandwidth
1 kHz
Isolation
Yes
Supply Power
15 - 30 V DC
19 - 29 V DC

Models

DSCA39-01
0-10 V Input, 4-20 mA Output
DSCA39-02
± 10 V Input, 4-20 mA Output
DSCA39-03
0-10 V Input, 0-20 mA Output
DSCA39-04
± 10 V Input, 0-20 mA Output
DSCA39-05
0-20 mA Input, 0-20 mA Output
DSCA39-07
±10 V Input, ± 20 mA Output

Downloads

DSCA39
DSCA Series
DSCA Dimensions
AN101 RMS_Voltage_Current
AN121 RiseTime vs BW
AN126 Tuning_Surge_Tank_Level_Control_Loops
AN128 RMS Revisited
AN129 Harmonics and utility costs
AN801 DSCA Calibration Procedure
Hysteresis Specifications
Faraday's Law of Induction
Signal-to-Noise Ratio, SNR
Data Acquisition Systems Accessories
Signal Conditioner Surge Withstand Capability
Signal Conditioning Measured vs Combinational Error
When Good Grounds Go Bad
Why Should Sensors Be Isolated